Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0724-01372
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/13/2024 | Site Zoning | APPROVED | |||
12/13/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/05/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The use of the Clean Air System to reduce the required amount of outside air to ventilate the bar is an alternative design. Submit an appeal to the building official to document the design. The documentation shall include the design assumptions and occupancy conditions, design contaminant levels, equipment performance, and the required maintenance schedule. Reference: Sections 105 and 403.2 (exception), IMC 2018. (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/appeal_form4.pdf) | ||
12/05/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Specify the components of the hot water recirculation loop and show how they are to be installed. [Second comment: The revised plumbing plans do not indicate that the distance between the hot water source (the recirculating loop) and the lavatories is a maximum of 24” for a ½”pipe or 6” for a ¾” pipe. The hot water heater piping detail does not indicate the presence of a hot water recirculation loop and no components of a recirculation hot water recirculation loop are specified. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] | ||
12/13/2024 | Design Review | REVIEW COMPLETED | Design review approved. See attachments for more information. | ||
12/06/2024 | Historic | REVIEW COMPLETED | Historic review completed. No further historic review Contact Michael.Taku@tucsonaz.gov |
||
11/20/2024 | PDSD Application Completeness | REVIEW COMPLETED | |||
12/09/2024 | Site Engineering | REVIEW COMPLETED |