Permit Number: TC-COM-0724-01372
Parcel: 117061900

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0724-01372
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2024 Site Zoning APPROVED
12/13/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/05/2024 Commercial Mechanical REQUIRES RESUBMIT The use of the Clean Air System to reduce the required amount of outside air to ventilate the bar is an alternative design. Submit an appeal to the building official to document the design. The documentation shall include the design assumptions and occupancy conditions, design contaminant levels, equipment performance, and the required maintenance schedule. Reference: Sections 105 and 403.2 (exception), IMC 2018. (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/appeal_form4.pdf)
12/05/2024 Commercial Plumbing REQUIRES RESUBMIT Specify the components of the hot water recirculation loop and show how they are to be installed. [Second comment: The revised plumbing plans do not indicate that the distance between the hot water source (the recirculating loop) and the lavatories is a maximum of 24” for a ½”pipe or 6” for a ¾” pipe. The hot water heater piping detail does not indicate the presence of a hot water recirculation loop and no components of a recirculation hot water recirculation loop are specified. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
12/13/2024 Design Review REVIEW COMPLETED Design review approved. See attachments for more information.
12/06/2024 Historic REVIEW COMPLETED Historic review completed. No further historic review
Contact Michael.Taku@tucsonaz.gov
11/20/2024 PDSD Application Completeness REVIEW COMPLETED
12/09/2024 Site Engineering REVIEW COMPLETED