Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0724-01365
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2025 Bldg Permits - Post Review Express REVIEW COMPLETED
09/22/2025 Other Inspection Reports (Deferred Submittal) Express REVIEW COMPLETED Sports Lighting

Per Special Inspection Notes:
Please review notes and don’t need to resubmit.
Review Notes:

1. Field installed wiring feeding the 30A contactors from panel HA shall be at least 7 feet long using #10 AWG wire. We require this to reduce the fault current below 18KA for 30A contactors. 30A contactor short circuit current rating is only 18KA.

2. Field installed wiring feeding the 60A contactors from panel HA shall be at least 7 feet long using #6 AWG wire. We require this to reduce the fault current below 25KA for 60A contactors. 60A contactor short circuit current rating is only 25KA.

3. We also noted design load kW value is not correct for TLC-LED-1200 fixtures on A3 and A4 fixtures. This should be 3.51 kW, because there are three fixtures each of
1.17kW. Please see related EDG comments on project summary page 9 of the submittal.