Permit Number: TC-COM-0724-01357
Parcel: 14117008A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01357
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/31/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 7/30/2024 11:47:09 PM
All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block of the sheet. Please include with the resubmittal a separate response letter numbered or itemized to correspond to each of the noted plan review comments items.
1. CS.00 (Cover Sheet)- In the Index of Drawings, Sheet SC.01 Code Data is listed however no sheet was included with the submitted set. Provide this sheet or indicate the code compliance data elsewhere in the plans. Additional comments may be required once received. Include the following information at a minimum:
i. Provide a written description of the work.
ii. Indicate what work will be provided under deferred submittals, and what work will be under separate permit submittals.
iii. Indicate any special inspections required for the project.
iv. Indicate the building height and area of the proposed structure.
v. Indicate the building construction type.
vi. Provide the occupancy use groups, occupancy loads and sf area for each use.
vii. Indicate all work will be in accordance with the adopted codes as adopted by the City of Tucson and list the
codes indicated below.
◦ 2018 International Building Code
◦ 2018 International Energy Code
◦ 2018 International Fuel Gas Code
◦ 2018 International Mechanical Code
◦ 2018 International Plumbing Code
◦ 2017 National Electrical Code
◦ 2018 International Fire Code
◦ City of Tucson/ Pima County Outdoor Lighting Code
◦ ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)
2. CS.00 (Cover Sheet)- Correct the sheet index, Sheet A5.3 Section Details is listed twice in the index, Sheet M6.2 is listed in the index but missing from set, and sheet P2.1 is in set but not listed in the index.
3. LS1.0 (Life Safety Plan)- Show EM light on outside of exit doors on the life safety plan. Emergency lights are required on the exterior at the exit doors to illuminate the landings. 2018 IBC 1008.3.2 (5).






Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 7/20/2024 5:13:07 PM
General Comment. Tucson is misspelled in address of border template.
1. E2.1 could not locate Electrical Note #2.
2. E2.3 could not locate Electrical Note #6 and missing Electrical Note 7.
3. E3.0 could not locate Electrical Notes 3, 9, and 11.
4. E4.0 Panelboard HA MLO rating should match Main Bus rating.
5. E5.0 Tucson City requires short circuit calculations for all new panels. Need to get service fault current from local power company’s website which provides these values for standard service sizes.
6. E5.0 detail 1, One Line diagram feeder to panel HA is missing a neutral wire. Correct feeder.
7. E5.0 Need to explicitly state size of T1 transformer. Then confirm grounding size is correct for transformer.
8. E6.1 Lighting comchecks are not legible. Interior Lighting Comcheck shall be resubmitted. Should resubmit Exterior Lighting Comcheck.
9. E6.1 Exterior lighting calculation should be per Tucson City’s outdoor lighting requirements. Sheet E1.2 Photometric Site Plan is accepted in place of Tucson City exterior lighting requirement by this reviewer.






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/30/2024 8:28:35 PM
First Plumbing Review:
1). Plan Page P1.0: Missing Oil interceptor Vent. Add a vertical oil interceptor vent in accordance with -2018 IPC 1003.9 also see 905.4
2). Plan page P3.1: missing oil interceptor sizing calculations, add sizing calculations in accordance with -2018 IPC 1003.4.2.2
3). Plan page P4.0: Missing ASSE 1070 mixing valve for lavatories. Add ASSE 1070 mixing valve to fixture schedule. -2018 IPC 419.5
08/15/2024 Fire New Construction REQUIRES RESUBMIT Address SafeBuilt comments.
Questions: patricia.shelton@tucsonaz.gov
08/15/2024 Site Engineering REQUIRES RESUBMIT see zoning comments
08/13/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01357 - TD-DEV-0324-00092
7655 S HOUGHTON RD. – I-2
Trade Service and Repair: Major (1st Review)

TRANSMITTAL: August 13, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed

This site is located in the I-2 zone (UDC 4.7.30). Trade Service and Repair: Major is a allowed use in the zone (UDC Table 4.8-5), subject to use specific standards 4.9.4.X.1 and 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0324-00092, and the following comments need to be addressed.

2. Sheet SP0.1 the square footage shown within the footprint does not match what is shown on the DP.

3. Sheet SP0.1 the parking layout shown along the south side of the building does not match what is shown on the DP.

4. Sheet SP0.2 the parking layout shown along the south side of the building does not match what is shown on the DP.

5. Until the DP is approved by all review agencies Zoning cannot approve this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/15/2024 Water - PDSD REQUIRES RESUBMIT 1. Coordinate the location and size of the water meter and water service entrance to the building with the civil drawings. Water meters are not to be located within buildings.
2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.
07/16/2024 PDSD Application Completeness REVIEW COMPLETED