Permit Number: TC-COM-0724-01357
Parcel: 14117008A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01357
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/08/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer (from previous submittal TUC9579001.071624)
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/23/2024 9:15:45 PM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 1/8/2025 12:39:53 AM
A complete set of drawings must be provided for approval, not just the sheets that were modified. Please provide all of the sheets for the newly revised set.



Mechanical(M) Reviewer (from previous submittal TUC9579001.071624)
Jorge Valido
jvalido@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/29/2024 3:32:16 PM
1. General - As per: 232008 CC (Rita Ranch) Tucson, AZ - Project Manual Permit Set - 06-28-2024_v1.pdf - PAINT BOOTH PLANS (Under Separate Review and Permit)




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/2/2025 12:35:58 PM





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/5/2025 8:59:36 PM
Second Plumbing Review: Comments Remain
Unresolved-1). Plan Page P1.0: Missing Oil interceptor Vent. Add a vertical oil interceptor vent in accordance with -2018 IPC
1003.9 also see 905.4
Unresolved-2). Plan page P3.1: missing oil interceptor sizing calculations, add sizing calculations in accordance with -2018
IPC 1003.4.2.2
Unresolved-3). Plan page P4.0: Missing ASSE 1070 mixing valve for lavatories. Add ASSE 1070 mixing valve to fixture schedule. -2018 IPC 419.5
01/23/2025 Site Engineering REQUIRES RESUBMIT TC-COM-0724-01357
7655 S HOUGHTON RD

Site engineering comments are as follows:
1. Neither building square footage on Sheet CS.01 of TC-COM-0724-01357 matches that shown on Sheet C8 of the Development Package, TD-DEV-0324-00092.
2. The parking configuration on the south side of the building does not match this area of Sheet C8 of Development Package, TD-DEV-0324-00092.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
01/21/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01357 - TD-DEV-0324-00092
7655 S HOUGHTON RD. – I-2
Trade Service and Repair: Major (2nd Review)

TRANSMITTAL: January 21, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed

This site is located in the I-2 zone (UDC 4.7.30). Trade Service and Repair: Major is a allowed use in the zone (UDC Table 4.8-5), subject to use specific standards 4.9.4.X.1 and 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0324-00092, and the following comments need to be addressed.

2. This comment was not addressed. Sheet SP0.1 the square footage shown within the footprint does not match what is shown on the DP.

3. This comment was not addressed. Sheet SP0.1 the parking layout shown along the south side of the building does not match what is shown on the DP.

4. Until the DP is approved by all review agencies Zoning cannot approve this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/16/2025 Water - PDSD REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Coordinate the location and size of the water meter and water service entrance to the building with the civil drawings. Water meters are not to be located within buildings.]
2. Comment not addressed. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.]
3. Submit the complete drawing package for each review.
01/14/2025 Fire New Construction REVIEW COMPLETED
12/31/2024 PDSD Application Completeness Express REVIEW COMPLETED