Permit Number: TC-COM-0724-01357
Parcel: 14117008A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01357
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review PENDING ASSIGNMENT
N/A Fire New Construction PENDING ASSIGNMENT
N/A Site Engineering PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
N/A Water - PDSD PENDING ASSIGNMENT
01/08/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer (from previous submittal TUC9579001.071624)
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/23/2024 9:15:45 PM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 1/8/2025 12:39:53 AM
A complete set of drawings must be provided for approval, not just the sheets that were modified. Please provide all of the sheets for the newly revised set.



Mechanical(M) Reviewer (from previous submittal TUC9579001.071624)
Jorge Valido
jvalido@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/29/2024 3:32:16 PM
1. General - As per: 232008 CC (Rita Ranch) Tucson, AZ - Project Manual Permit Set - 06-28-2024_v1.pdf - PAINT BOOTH PLANS (Under Separate Review and Permit)




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/2/2025 12:35:58 PM





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/5/2025 8:59:36 PM
Second Plumbing Review: Comments Remain
Unresolved-1). Plan Page P1.0: Missing Oil interceptor Vent. Add a vertical oil interceptor vent in accordance with -2018 IPC
1003.9 also see 905.4
Unresolved-2). Plan page P3.1: missing oil interceptor sizing calculations, add sizing calculations in accordance with -2018
IPC 1003.4.2.2
Unresolved-3). Plan page P4.0: Missing ASSE 1070 mixing valve for lavatories. Add ASSE 1070 mixing valve to fixture schedule. -2018 IPC 419.5
12/31/2024 PDSD Application Completeness REVIEW COMPLETED