| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2024 | Commercial Plumbing | NOT REQUIRED | |||
| 08/01/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/25/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Indicate the generator OCPD amp rating feeding the transfer switch and verify if a grounding electrode system is required at the generator (separately derived system) per NEC 250.35. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||