Permit Number: TC-COM-0724-01352
Parcel: 11611005B

Address:
190 N SHANNON RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0724-01352
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2024 Commercial Plumbing NOT REQUIRED
08/01/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Indicate the generator OCPD amp rating feeding the transfer switch and verify if a grounding electrode system is required at the generator (separately derived system) per NEC 250.35.

Ref; 2018 IBC section 107.2.1, 2017 NEC
07/12/2024 PDSD Application Completeness Express REVIEW COMPLETED