Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2024 | Site Zoning | APPROVED | |||
08/13/2024 | Site Engineering | NOT REQUIRED | |||
08/13/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/29/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Building(B) Reviewer Janet Matz jmatz@safebuilt.com Denied Reason: Date Completed : 7/24/2024 11:33:04 PM 1. Sheet G1.0 (Cover Sheet). Indicate the following additional applicable codes listed under the Project Code Data: i. ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities. 2. Sheet G2.1 (Guidelines). Please clarify if there will be any remodeling to be done in the existing staff break room. The Guidelines Floor Plan shows this area being crosshatched similar to the New Cath Lab work area. Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 7/26/2024 9:31:39 AM 1. General - Provide Energy Heat Load Calculations for new area. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. |
||
08/06/2024 | Fire New Construction | REVIEW COMPLETED | |||
07/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |