Permit Number: TC-COM-0724-01342
Parcel: 10610005D

Address:
2020 W PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0724-01342
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2024 Commercial Plumbing NOT REQUIRED
07/31/2024 Site Engineering NOT REQUIRED
08/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/31/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. In accordance with SECTION 107 of the 2018 IBC and the PDSD Building Plan Requirements, a the below requested drawings and information demonstrating the scope of work shall be provided. All plans must be sealed and signed by an Architect or Engineer registered in the State of Arizona. Note. The term ‘building plans may refer to structural, electrical, plumbing, or any other trade regulated by the associated suite of codes adopted by the City of Tucson.
2. Please provide a cover Sheets General Project information including address, location map and square footage. A complete Code Analysis should also be present detailing the type of construction, occupancy classification(s), occupancy loads, exiting requirements, fire sprinklers and fire alarms. The cover sheet must include a legend of symbols and abbreviations used throughout the plan set. IBC 107.2.1
3. Please provide architectural drawings to include an architectural Site plan showing the building on the lot. IBC 107.2.6
4. Please provide a dimensioned architectural floor plan of the original building show the location of this new office building. IBC 107.2.1
5. Please provide an Exiting/ Life Safety plan to include paths of egress, travel distance. Etc IBC 107.2.3
a. The total number of occupants for the story or floor is shown. IBC 107.2.3
b. The number of occupants is shown for every room and space. IBC 107.2.3
c. The occupant load factor and area are shown for every room and space. IBC 1004.5
d. The occupant load factor used reflects the use/function of the space. IBC 1004.5
6. Please note: The plans are incomplete as submitted and further comments could arise.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Include branch circuit designations, panel schedules, Indicate clearly all light fixture symbols and luminaire schedule. Provide compliance with the 2018 IECC for lighting.
Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2018 IECC.
07/30/2024 Commercial Mechanical REQUIRES RESUBMIT Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
08/02/2024 Fire New Construction REQUIRES RESUBMIT Address building comments.
Questions: patricia.shelton@tucsonaz.gov
07/23/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01342
2020 W PRINCE RD. – I-1
2-story modular office system ( 1st Review)

TRANSMITTAL: July 23, 2024
This site is located in the I-1 zone (4.7.29).

1. As the proposed 2-story modular office system is adding square footage to the site a commercial site plan (development package) is required. UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/11/2024 PDSD Application Completeness REVIEW COMPLETED