Permit Number: TC-COM-0724-01336
Parcel: 12909146C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01336
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2024 Site Zoning APPROVED
08/14/2024 Water - PDSD APPROVED
08/15/2024 Site Engineering NOT REQUIRED
08/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/22/2024 External Reviewers - Willdan REQUIRES RESUBMIT ekulik@willdan.com
1. Sheet A1.0 Provide dimensions of each room. Provide number of occupants in each room per IBC Chapter 10.
2. Sheet A1.0 Provide occupant load for conference room. 2 exits are required for spaces over 49 occupants. IBC Table 1006.2.1
3. Sheet A1.0 Provide occupant load for conference room. 2 exits are required for spaces over 49 occupants. IBC Table 1006.2.1
4. Sheet A1.0 Provide the number of exits from conference rooms per Chapter 10 section 1003.
5. Sheet A2.0 Provide the manufacturer of the Ceiling Grid and details for the installation.
6. Sheet A3.0 Provide attachment details for new walls. Top Track and Bottom Track.
7. Sheet A3.1 Show ADAAG Compliance for Break Area.
8. Sheet M1.0 Provide documentation that the Mechanical System complies with the 2018 IEEC.
9. Sheet M1.0 Coordinate Mechanical Plan with Architectural Plan. Appears to be difference in floor plans.
10. Sheet P0.0 Show location of required drinking fountains based on occupant load. Comply with ADAAG drinking fountain requirements.
11. Sheet E 4.0 Provide details for attaching new light fixtures to new grid ceiling.
08/08/2024 Fire New Construction REVIEW COMPLETED
07/15/2024 PDSD Application Completeness REVIEW COMPLETED