Permit Number: TC-COM-0724-01324
Parcel: 12704046A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0724-01324
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2024 Commercial Building APPROVED
07/29/2024 Commercial Mechanical APPROVED
07/29/2024 Site Engineering APPROVED
07/22/2024 Site Zoning APPROVED
07/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; One Line Diagram. Could not locate the ‘Grounding Detail’ as shown on the electrical service ground.

2 Provide compliance with the 2018 IECC for the lighting.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC
07/29/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
07/30/2024 Fire New Construction REVIEW COMPLETED
07/09/2024 PDSD Application Completeness Express REVIEW COMPLETED