Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0724-01324
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2024 | Commercial Building | APPROVED | |||
| 07/29/2024 | Commercial Mechanical | APPROVED | |||
| 07/29/2024 | Site Engineering | APPROVED | |||
| 07/22/2024 | Site Zoning | APPROVED | |||
| 07/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; One Line Diagram. Could not locate the ‘Grounding Detail’ as shown on the electrical service ground. 2 Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC |
||
| 07/29/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
||
| 07/30/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 07/09/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |