Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0724-01324
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/25/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The grounding detail shows the Grounding Electrode Conductor terminated in the service disconnect, not the Meter Base. Provide compliance with NEC art 250.24(A). 2 The ComCheck lighting certificate could be located in the submitted plan documents. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
| 09/25/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Section C404.5, IECC 2018 restricts the distance from the hot water source to the connection to a public lavatory. For a ½” hot water supply, the maximum distance is 24 inches. This is typically accomplished by using either a circulating hot water loop (the loop becomes the hot water source) or a tankless water heater located under the lavatory. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] | ||
| 09/12/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |