Permit Number: TC-COM-0724-01324
Parcel: 12704046A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0724-01324
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The grounding detail shows the Grounding Electrode Conductor terminated in the service disconnect, not the Meter Base. Provide compliance with NEC art 250.24(A).

2 The ComCheck lighting certificate could be located in the submitted plan documents.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
09/25/2024 Commercial Plumbing REQUIRES RESUBMIT Section C404.5, IECC 2018 restricts the distance from the hot water source to the connection to a public lavatory. For a ½” hot water supply, the maximum distance is 24 inches. This is typically accomplished by using either a circulating hot water loop (the loop becomes the hot water source) or a tankless water heater located under the lavatory. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
09/12/2024 PDSD Application Completeness Express REVIEW COMPLETED