Permit Number: TC-COM-0724-01319
Parcel: 12106001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01319
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2026 Site Engineering Standard APPROVED
01/20/2026 Site Zoning Standard APPROVED
01/20/2026 Water - PDSD Standard APPROVED
01/08/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/07/2026 Commercial Building Standard REQUIRES RESUBMIT January 7, 2026
1st Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-25-118

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

ARCHITECTURAL COMMENTS

Sheet A2

1. The revised set of plans included an exit access stair. The documents lack sufficient information to verify compliance with the 2018 IBC. Submit plans and details indicating stair width, riser and tread dimensions, landings, headroom, handrails, guards, and materials. [Ref. IBC 2018 Sec. 1005, 1011]

2. The revised set of plans included an ADA ramp at the exit to the east of the tenant space. The submitted documents do not provide sufficient information to verify compliance with the 2018 IBC and referenced accessibility standards. At a minimum, submit plans, profiles, and details indicating ramp slope, rise, width, landings, cross slope, handrails, edge protection, surface materials, and transitions. [Ref. IBC 2018 Sec. 1009, 1012, ICC A117.1-2009]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/07/2026 Commercial Electrical Standard REQUIRES RESUBMIT January 7, 2026
1st Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-25-118

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

ARCHITECTURAL COMMENTS

Sheet A2

1. The revised set of plans included an exit access stair. The documents lack sufficient information to verify compliance with the 2018 IBC. Submit plans and details indicating stair width, riser and tread dimensions, landings, headroom, handrails, guards, and materials. [Ref. IBC 2018 Sec. 1005, 1011]

2. The revised set of plans included an ADA ramp at the exit to the east of the tenant space. The submitted documents do not provide sufficient information to verify compliance with the 2018 IBC and referenced accessibility standards. At a minimum, submit plans, profiles, and details indicating ramp slope, rise, width, landings, cross slope, handrails, edge protection, surface materials, and transitions. [Ref. IBC 2018 Sec. 1009, 1012, ICC A117.1-2009]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/07/2026 Commercial Mechanical Standard REQUIRES RESUBMIT January 7, 2026
1st Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-25-118

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

ARCHITECTURAL COMMENTS

Sheet A2

1. The revised set of plans included an exit access stair. The documents lack sufficient information to verify compliance with the 2018 IBC. Submit plans and details indicating stair width, riser and tread dimensions, landings, headroom, handrails, guards, and materials. [Ref. IBC 2018 Sec. 1005, 1011]

2. The revised set of plans included an ADA ramp at the exit to the east of the tenant space. The submitted documents do not provide sufficient information to verify compliance with the 2018 IBC and referenced accessibility standards. At a minimum, submit plans, profiles, and details indicating ramp slope, rise, width, landings, cross slope, handrails, edge protection, surface materials, and transitions. [Ref. IBC 2018 Sec. 1009, 1012, ICC A117.1-2009]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/07/2026 Commercial Plumbing Standard REQUIRES RESUBMIT January 7, 2026
1st Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-25-118

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

ARCHITECTURAL COMMENTS

Sheet A2

1. The revised set of plans included an exit access stair. The documents lack sufficient information to verify compliance with the 2018 IBC. Submit plans and details indicating stair width, riser and tread dimensions, landings, headroom, handrails, guards, and materials. [Ref. IBC 2018 Sec. 1005, 1011]

2. The revised set of plans included an ADA ramp at the exit to the east of the tenant space. The submitted documents do not provide sufficient information to verify compliance with the 2018 IBC and referenced accessibility standards. At a minimum, submit plans, profiles, and details indicating ramp slope, rise, width, landings, cross slope, handrails, edge protection, surface materials, and transitions. [Ref. IBC 2018 Sec. 1009, 1012, ICC A117.1-2009]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/20/2026 Fire New Construction Standard REVIEW COMPLETED
12/30/2025 PDSD Application Completeness Express REVIEW COMPLETED