Permit Number: TC-COM-0724-01319
Parcel: 12106001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01319
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2024 Water - PDSD APPROVED
08/08/2024 Site Engineering NOT REQUIRED
09/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/09/2024 External Reviewers - Stantec REQUIRES RESUBMIT July 19, 2024
1st Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-24-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

GENERAL COMMENTS

1. The plan-set provided does not include an odor mitigation plan and methods for odor control requirements. Please provide. [Ref. City of Tucson Ordinance 11828 Sec. 4.9.9 E.1.I.]


ARCHITECTURAL COMMENTS

General

1. Please note on the cover of the drawings that special inspection is required for wood roof strengthening members. Please also make sure that the owner or their legal representative signs the form the form provided is missing this signature.

Sheet A2

1. The maximum common path of egress travel distance of 75’ appears to be exceeded at the ‘Recreational Area’ and the back offices in the southeast corner of the tenant space. When measured at the given scale the ‘Recreational Area’ indicates 102’ before occupants have separate and distinct access to two exits. The back offices vary from 89’ to 105’ common path of travel distance.

Sheet A3

1. Please indicate the 5’ turning space in the new restroom. [Ref. ICC A117.1-2009 Sec. 304.3.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please provide an energy conservation compliance report for the new mechanical system. [Ref. IECC 2018 Sec. C403]

Sheet M1

1. Unit AC-2 on the Air Device and Balance Table indicates 4,000cfm which conflicts the Air Conditioning Unit Schedule on sheet M3 that indicates 2,000cfm for AC-2. Please revise.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/02/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01319
5851 E SPEEDWAY BL Unit: 101– C-2
Marijuana Facility: Dispensary (1st Review)

TRANSMITTAL: August 2, 2024

Resubmittal requires a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Marijuana Facility: Dispensary is an allowed use in the zone (UDC Table 4.8-4), subject to a Mayor and Council Special Exception Procedure, Section 3.4.4 and Use Specific Standard 4.9.9.E.1

1. Until the special exception procedure is completed and approved Zoning cannot approve this building permit. Special exception requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/08/2024 Fire New Construction REVIEW COMPLETED
07/09/2024 PDSD Application Completeness Express REVIEW COMPLETED