Permit Number: TC-COM-0724-01319
Parcel: 12106001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01319
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/15/2025 Commercial Mechanical Standard REQUIRES RESUBMIT The submitted odor control plan will not mitigate the spread of odors beyond the building envelope. Reference: City of Tucson Ordinance 11828 Sec. 4.9.9.E.1.I
12/31/2024 External Reviewers - Stantec REQUIRES RESUBMIT December 31, 2024
2nd Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: RELEAF 85712 MARIJUANA DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01319
Stantec Project Number: 185215066
Stantec File Number: TUC-24-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 9,782 193 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening members.

GENERAL COMMENTS

1. Previous Comment: The plan-set provided does not include an odor mitigation plan and methods for odor control requirements. Please provide. [Ref. City of Tucson Ordinance 11828 Sec. 4.9.9 E.1. I.] Still Required: The exhaust fan in the bathroom must include odor mitigation. Please revise.



ARCHITECTURAL COMMENTS

General

1. Previous Comment: Please note on the cover of the drawings that special inspection is required for wood roof strengthening members. Please also make sure that the owner or their legal representative signs the form the form provided is missing this signature. Still Required: The required special inspection was not noted on the cover page of the plan-set.

Sheet A2

1. Previous Comment: The maximum common path of egress travel distance of 75’ appears to be exceeded at the ‘Recreational Area’ and the back offices in the southeast corner of the tenant space. When measured at the given scale the ‘Recreational Area’ indicates 102’ before occupants have separate and distinct access to two exits. The back offices vary from 89’ to 105’ common path of travel distance. Still Required: The “Recreational Area” still has a common path of egress travel distance of 102’. This portion was not addressed in the revised plan.

Sheet A3

1. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Addressed.

Sheet M1

1. Addressed.

PLUMBING COMMENTS

There are no comments.


ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/17/2025 Site Zoning REQUIRES RESUBMIT 1. Ped UDC 4.9.9.E.1.I an Odor Mitigation Plan is demonstrating compliance with odor control requirements is required when a modification is made to a marijuana facility, or the facility operation, that has the potential to impact the nature of degree of odor. Zoning cannot approve until an Odor Mitigation Plan has been submitted and the Commercial Mechanical reviewers has approved the mechanical plans in accordance with the Odor Mitigation Plan.

Loran Shamis
Loran.Shamis@tucsonaz.gov
12/20/2024 PDSD Application Completeness Express REVIEW COMPLETED