Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0724-01316
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2024 | Site Zoning | APPROVED | |||
| 07/29/2024 | Site Engineering | NOT REQUIRED | |||
| 07/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/29/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. 1. Please amend plans to provide a legible designer’s seal, signature, and date signed on all sheets. IBC 107.1 2. Please provide a detailed description of the work involved and purpose in this permit’s scope. IBC 105.3 For example, this permit will be a change of use from IRC structure to IBC R-4 Condition 1 Assisted Living Facility or , this permit will be a change of use from IRC structure to IBC R-4 Condition 2 Assisted Living Facility 3. Please amend the Code Analysis to indicate if this R-4 Occupancy is a Condition 1 or Condition 2 occupancy. IBC 302. For example, • 310.5.1 Condition 1. This occupancy condition shall include buildings in which all persons receiving custodial care, without any assistance, are capable of responding to an emergency situation to complete building evacuation. • 310.5.2 Condition 2. This occupancy condition shall include buildings in which there are any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation 4. Please amend plans to provide a dimensioned floor plan with all rooms named to include on plans the following information: A. Illumination with emergency backup power is required in all components of the means of egress system. IBC 1008 B. Please show accessible entrance to include door width, and thresholds, Thresholds in existing buildings shall have beveled edges and a maximum height of 3/4-in. C. Please show on plans; Smoke alarms shall be installed at each story, in each sleeping room, and outside of each separate sleeping area in the immediate vicinity of bedrooms [R314.3]. In addition, these shall be hard-wired with battery backup [R314.4] and interconnected [R314.5]. D. Please Identify the sill height window style and dimensions for all bedroom egress windows. IBC 107.2.1 5. Please amend plans to provide drawings, details and notes indicating compliance with IBC 1107.3 Accessible spaces. For example, Rooms and spaces available to the public or available for use by residents and serving Accessible units, Type A units or Type B units shall be accessible. ccessible spaces shall include toilet and bathing rooms, kitchen, living and dining areas and any exterior spaces, including patios, terraces and balconies 6. Please amend plans to show compliance with IBC 1107.6.4 A. 1107.6.4.1 Accessible units. In Group R-4, Condition 1, at least one of the sleeping units shall be an Accessible unit. In Group R-4, Condition 2, at least two of the sleeping units shall be an Accessible unit. B. 1107.6.4.2 Type B units. C. In structures with four or more sleeping units intended to be occupied as a residence, every sleeping unit intended to be occupied as a residence shall be a Type B unit. 7. Please provide an enlarged drawing to include details and notes of the Accessible bathroom in compliance with the following 2009 ICC A117.1 Sections. A. 606 Lavatories and sinks B. 607 Bathtubs C. 608 Shower compartments D. 609 Grab Bars E. 610 Seats Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 07/23/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The electrical plan shows the addition of a 20 amp branch circuit, relocating the ac unit and other lighting modifications. Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Include branch circuit designations, panel schedules, Indicate clearly all light fixture symbols. Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, |
||
| 07/29/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed 2. Show how mechanical ventilation is to be provided for the living areas. Reference: Sections R403.6 and R502.1.1.2, IECC 2018, and Sections 403.1 and 403.3.2.1, IMC2018. |
||
| 07/29/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf. | ||
| 07/30/2024 | Fire New Construction | REQUIRES RESUBMIT | Address comments from Commercial Building. questions: patricia.shelton@tucsonaz.gov |
||
| 07/08/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |