Permit Number: TC-COM-0724-01309
Parcel: 11310020A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01309
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2024 Commercial Electrical APPROVED
08/15/2024 Commercial Structural APPROVED
08/08/2024 Site Engineering APPROVED
08/01/2024 Site Zoning APPROVED
08/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/08/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Revise the heating and cooling load calculations to justify the additional heating/cooling capacity of HP-1 to condition the space covered by the existing AC-2. Reference: Section C403.1.1 and C502.2.3, IECC 2018
2. Revise the mechanical design as required to avoid using the egress areas as return air ducts. Reference: Section 601.2, IMC 2018.
08/10/2024 Commercial Plumbing REQUIRES RESUBMIT The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
08/02/2024 Fire New Construction REVIEW COMPLETED
07/08/2024 PDSD Application Completeness Express REVIEW COMPLETED