Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0724-01309
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2024 | Commercial Electrical | APPROVED | |||
| 08/15/2024 | Commercial Structural | APPROVED | |||
| 08/08/2024 | Site Engineering | APPROVED | |||
| 08/01/2024 | Site Zoning | APPROVED | |||
| 08/15/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/08/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Revise the heating and cooling load calculations to justify the additional heating/cooling capacity of HP-1 to condition the space covered by the existing AC-2. Reference: Section C403.1.1 and C502.2.3, IECC 2018 2. Revise the mechanical design as required to avoid using the egress areas as return air ducts. Reference: Section 601.2, IMC 2018. |
||
| 08/10/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. | ||
| 08/02/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 07/08/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |