Permit Number: TC-COM-0724-01307
Parcel: 13213034D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01307
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 8/19/2024 2:40:41 PM

1. (UNRESOLVED) - General - Provide Energy Heat Load Calculations - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
i. Provide Energy Heat Load Calculations. Calculations must be an APPROVED (by AHJ) method. or as stated in - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
ii. Plan Sheet M1.0 - 2018 IECC does not have 503.2.2 - 2018 IECC
08/15/2024 PDSD Application Completeness Express REVIEW COMPLETED