Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0724-01296
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/30/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The submitted drawing cannot be reviewed without additional information and verification of the connected gas loads (e.g. a typical, large pool heater has a load of 400,000 BTUH, a water heater with a load of 200,000 BTUH or greater is a boiler, and a ½” carbon steel pipe can supply 9300 BTUH at 171 feet with a pressure drop of only 0.5” WG). Revise the natural gas pipe replacement drawing to show: 1. The location of the gas meter 2. The gas delivery pressure (e.g., 7” WG, 2 PSIG, or 5 PSIG) 3. The gas load for each piece of equipment in BTUH 4. The developed pipe length from the meter to each piece of equipment 5. The size and material of each pipe segment. 6. The location and downstream pressure of any pressure reducing valves. |
||
| 07/10/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |