Permit Number: TC-COM-0724-01295
Parcel: 11627504B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01295
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2024 Site Engineering APPROVED
08/01/2024 Site Zoning APPROVED
08/08/2024 Water - PDSD APPROVED
08/08/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/05/2024 External Reviewers - Stantec REQUIRES RESUBMIT July 17, 2024
1st Review

Seaver Franks
Attn: Rick Huch/Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS CLUBHOUSE
TENNAT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01295
Stantec Project Number: 185215066
Stantec File Number: TUC-24-091

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 15,887 448 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. Please clarify if the opening of the exterior at the ‘New Bar’ is existing or new. If new, please provide an engineered structural design for this opening. [Ref. IBC 2018 Sec. 1603]


ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

Sheet A0.0

1. Please remove the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] from the deferred submittal list as they are to be submitted as a separate permit (not a deferred submittal).

2. The occupant load factor for the ‘Multi-Purpose Room’ is indicated as 50. This room should be calculated at 15 net (Assembly – unconcentrated). Please revise.

3. The Exit Plan indicates that the maximum common path of travel distance of 75’ is exceeded at the New Multi-Purpose Room. When scaled the common path of travel distance from this room is 82’3”. Please revise. [Ref. IBC 2018 Sec. 1006.2.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance report for the interior lighting. [Ref. IECC 2018 Sec. C405.3]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/02/2024 Fire New Construction REVIEW COMPLETED
07/08/2024 PDSD Application Completeness REVIEW COMPLETED