Permit Number: TC-COM-0724-01289
Parcel: 106050880

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0724-01289
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2025 Commercial Structural APPROVED
04/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review MASTER SET LOCATED AT: TC-COM-0624-01263, WITH REVIEWS TO BE PERFORMED ON: TC-COM-0724-01277, TC-COM-0724-01278, TC-COM-0724-01279, TC-COM-0724-01280, TC-COM-0724-01281, TC-COM-0724-01282, TC-COM-0724-01289, TC-COM-0724-01290, , TC-COM-0724-01291, TC-COM-0724-01292, TC-COM-0724-01293Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Electrical:
1. Designate the circuit number, that corresponds to the panel schedule, at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
2. Reference Sheet E-1.1. The circuit numbers associated with the outdoor lighting fixtures are EV-18 and EV-17. From the EV panel schedule, circuit numbers 18 and 17 are listed as ‘spare’. Update the panel schedule and load calculations to show the outdoor lighting circuit numbers correctly.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

>>> These comments were not fully addressed:
Outdoor Lighting:
1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show full cutoff fixtures were located with 25 feet from the property line OLC 401.3.3. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. In the table, “total” means the sum of shielded and unshielded light.
a. Table 401.1 lists maximum lumens allowed for 1 acre and must be adjusted based on the actual parcel acreage.
3. As part of your submittal, indicate the Lighting Area the parcel belongs (Missing lighting area from calculations. E3, E3a, etc.?). See Table 401.1.
4. Provide your lumens calculation as to the shielded/full cutoff and unshielded allowed for that parcel.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/27/2025 PDSD Application Completeness Express REVIEW COMPLETED