Permit Number: TC-COM-0723-01864
Parcel: 13416205D

Address:
7145 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01864
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Site Zoning APPROVED
09/06/2023 Water - PDSD APPROVED
08/02/2023 Site Engineering NOT REQUIRED
09/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 8/10/2023 12:34:44 PM
1. Refer to Structural Calculations submitted. Sheet C-32 shows member W14x34 failing in bending by 6.8% and have excessive deflections. Verify and submit response.

2. Refer to Structural Calculations submitted. Sheet C-35 shows member W14x34 failing in bending by 17.3% and have excessive deflections. Verify and submit response.

3. Refer to Structural Calculations submitted. Sheet C-38 shows member W14x34 failing in bending by 8.4% and have excessive deflections. Verify and submit response.

4. Refer to Structural Calculations submitted. Sheet C-41 shows member W14x34 failing in bending by 13.3% and have excessive deflections. Verify and submit response.

5. DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.

If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:

* To be reviewed by design professional in responsible charge.

* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.

* They shall be submitted for review by the building official.

* Shall not be installed until approved by building official.

Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 8/4/2023 3:14:57 PM
1. Sheet G001: The base allowable area is incorrect. Since non-separated mix use is being used, the most restrictive base allowable area is required to be used. The A-3 use is the most restrictive. Provide a corrected allowable base area.

2. Sheet G003: Provide clarification as to why both the E and I-4 occupancy classification is being used? If the children are always going to be under 2.5 years of age classify it as an E. If the ages are going to be unknown and the amount of children fluctuate frequently, used the I-4 designation.

3. Sheet G003: Rooms that are designated at I-4 use are required to have not less than two exits. Provide additional exits in accordance with Section 1006.2.2.4.

4. General: Provide clarification on the uses of the adjacent tenant spaces to ensure proper tenant separation.

5. Sheet A102:8.Exercise equipment is required have clear floor space for access. Ensure clear floor space in accordance with Section 236.1 of the 2010 ADAAG.

6. Sheet A102: Provide section detail drawings of the exercise platforms. It appears that the ramps may not meet the maximum slope requirements for accessibility in accordance with Section 1012.2.

7. Sheet A102: It appears that the minimum aisle width have not been maintained between the back of the equipment and the next platform. Provide evidence of compliance in accordance with Section 1018.

8. All RCP: Indicate the location of all EXIT and EXIT directional signage within the Life Safety Plan. Coordinate these locations with the electrical designer. (2018 IBC Sec. 1008 and 1013)



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 8/6/2023 1:44:00 AM
1. Room# 104, 110,111,133,135 is above the refrigeration concentration limit (MMC2018,1104.4)

2. Provide ventilation calculations (MMC2018,403.3.1.1.1)

3. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm for VFC-1 & VFC-5 (MMC2018,606.2.1)

4. Duct smoke detectors shall be tied into the fire alarm system (MMC2018,606.4.1)




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/10/2023 5:43:28 PM
Electrical Review of Chuze Fitness
By: Ron Ross PE
Electrical approved with the following comments to correct or revise for construction set.

E001 ELECTRICAL SITE PLAN: Not included in set, but E110 sheet seemed sufficient.

E110 ELECTRICAL LIGHTING FLOOR PLAN: Could not locate Keynotes 2, 6, and 12.

E120 ELECTRICAL ROOF POWER PLAN: Could not locate Keynote 3.

E401 ENLARGED ELECTRICAL PLANS: Could not locate Keynotes 10, 11, 15, 17, 21, and 22.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 10:17:12 PM
First Plumbing Review:
1). Plan page P601 water heater schedule list a EWH-1 point of use EEmax water heater, there is not a EWH-1 shown on the water piping plan P401, and this doesn't correlate with the existing 1" hot water system shown supplying the hot piping in the
remodeled areas. See P111 & P401. plan pages need to correlate -IPC 106.3.1

2). Lavs on P601 need ASSE 1070 mixing valves - IPC 419.5

3). P602 trap primer detail needs a shut off valve - IPC 606.2
08/13/2023 Fire New Construction REVIEW COMPLETED
08/02/2023 PDSD Application Completeness REVIEW COMPLETED