Permit Number: TC-COM-0723-01864
Parcel: 13416205D

Address:
7145 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0723-01864
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/25/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/19/2023 10:00:14 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/19/2023 10:55:25 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/20/2023 9:28:39 PM
Approved/subject to field approval




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/10/2023 5:43:28 PM
Electrical Review of Chuze Fitness
By: Ron Ross PE
Electrical approved with the following comments to correct or revise for construction set.

E001 ELECTRICAL SITE PLAN: Not included in set, but E110 sheet seemed sufficient.

E110 ELECTRICAL LIGHTING FLOOR PLAN: Could not locate Keynotes 2, 6, and 12.

E120 ELECTRICAL ROOF POWER PLAN: Could not locate Keynote 3.

E401 ENLARGED ELECTRICAL PLANS: Could not locate Keynotes 10, 11, 15, 17, 21, and 22.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 9/23/2023 5:41:28 PM
Second Plumbing Review: OK
1). Resolved-Plan page P601 water heater schedule list a EWH-1 point of use EEmax water heater, there is not a EWH-1 shown on the water piping plan P401, and this doesn't correlate with the existing 1" hot water system shown supplying the hot piping in the remodeled areas. See P111 & P401. plan pages need to correlate -IPC 106.3.1

2). Resolved- on P601 need ASSE 1070 mixing valves - IPC 419.5

3). Resolved-P602 trap primer detail needs a shut off valve - IPC 606.2
09/18/2023 PDSD Application Completeness REVIEW COMPLETED