Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0723-01858
Parcel: 10409218A

Address:
4151 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0723-01858
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/03/2023 Commercial Electrical REQUIRES RESUBMIT Please address the following electrical plan review comments and provide a written response.

1 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code, (OLC).

Be advised, if this project falls into the use per OLC section 701.3, please specify and comply with sections 701.3, 701.4, 701.5.

2 Show the location of the 20 amp disconnect switch, transformer, panel ‘A’, GFI receptacles and panel ‘LP2B’ on the plan.

3 Show Lighting controls and verify curfew requirements per Outdoor Lighting Code if applicable. OLC section 403.5.

4 Provide a Grounding Electrode System at the temporary tent structure and ground to panel ‘A’ and bond to the Equipment Ground as required per NEC art 250.32.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
08/02/2023 PDSD Application Completeness REVIEW COMPLETED