Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0723-01831
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/23/2023 | Commercial Electrical | APPROVED | |||
08/30/2023 | Commercial Plumbing | APPROVED | |||
09/01/2023 | Commercial Structural | APPROVED | |||
09/01/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/30/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Ventilation for kitchens in private dwellings requires a minimum of 25 CFM (continuous operation) or 100 CFM (intermittent operation) of mechanical exhaust per room with no recirculation of air. If the proposed hood does not discharge to the outside, provide a general exhaust that does terminate outside. Reference: Section 403.3.2.3 and exception 1, Section 505.3, IMC 2018. | ||
07/28/2023 | PDSD Application Completeness | REVIEW COMPLETED |