Permit Number: TC-COM-0723-01831
Parcel: 117060210

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01831
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2023 Commercial Electrical APPROVED
08/30/2023 Commercial Plumbing APPROVED
09/01/2023 Commercial Structural APPROVED
09/01/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/30/2023 Commercial Mechanical REQUIRES RESUBMIT Ventilation for kitchens in private dwellings requires a minimum of 25 CFM (continuous operation) or 100 CFM (intermittent operation) of mechanical exhaust per room with no recirculation of air. If the proposed hood does not discharge to the outside, provide a general exhaust that does terminate outside. Reference: Section 403.3.2.3 and exception 1, Section 505.3, IMC 2018.
07/28/2023 PDSD Application Completeness REVIEW COMPLETED