Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Approved
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0723-01822
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Approved
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2024 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
04/15/2024 | County Health Inspection (Deferred Submittal) | REVIEW COMPLETED | |||
04/15/2024 | PDSD Application Completeness | REVIEW COMPLETED |