Permit Number: TC-COM-0723-01821
Parcel: 106050890

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01821
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2023 Commercial Structural APPROVED
07/27/2023 Site Zoning APPROVED
07/28/2023 Site Engineering NOT REQUIRED
08/31/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/22/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Provide detailed information as to the electrical scope of work required to restore the unit to a safe and code compliant condition. “Storage fire damage repair” is not detailed enough.

2. Provide a complete electrical power and lighting floor plan showing all replaced electrical devices, luminaires, smoke detectors, and branch circuit wiring circuit and panel designation.

3. The panel schedule needs to be more specific in identifying assigned circuits, NEC 408.4.

4. Show all GFI protected receptacles, as required per NEC art 210.

5. Provide for Tamper resistant receptacles replacements, NEC 406.12, 210.

6. Is the new sub panel replacement ‘Like for Like’ ? If not, provide an electrical line diagram showing the panel feeder size and type and overcurrent protection and load calculations.

7. Provide compliance with the 2012 City of Tucson Outdoor Lighting Code if applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC
07/30/2023 Fire New Construction REVIEW COMPLETED
07/27/2023 PDSD Application Completeness Express REVIEW COMPLETED