Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0723-01811
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Verify that the MH pedestals are rated as suitable for use as service equipment, NEC 550.32(A). 2. Provide grounding electrode systems for the Pedestals, NEC 250.32, 550.32. 3. Indicate the service riser conductor quantity, sizes and types. 4. Identify the unit(s) for this permit on the plans and correlate with the Meter in the new electrical service. The application info states 1201 E Mossman, unit #21. The electrical plan shows 2 units.. Please clarify. 5. Verify that the existing electrical services on the premises are fed overhead by the utility. If not, apply for an underground electrical service waiver, to be approved by the building official as required per 2018 IBC amendment section 112.1.1. Ref; 2018 IBC section 107.2.1, IBC Amendment 112.1.1, 2017 NEC. |
||
| 11/16/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |