Permit Number: TC-COM-0723-01799
Parcel: 116150810

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01799
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2023 Commercial Structural APPROVED
08/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide a minimum exhaust flow rate of 20 CFM per shower head if the exhaust is continuous, 50 CFM per shower head if the exhaust is intermittent. This exhaust flow rate is in addition to the exhaust required for the water closet. Note: as a public shower/restroom, the minimum exhaust flow rate for the water closet will be 50 CFM. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018.
2. Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2018.
08/28/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Coordinate the plumbing schedule, plans, and riser diagrams (i.e. the showers are called out as P-1 on the floor plan and riser diagrams but P-8 on the fixture schedule). Reference: Section 107.2.1, IBC 2018.
2. How will the circuit setter for the new HHR be set? Will the recirculation pump need to be replaced?
07/30/2023 Fire New Construction REVIEW COMPLETED
07/26/2023 PDSD Application Completeness Express REVIEW COMPLETED