Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0723-01794
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/22/2023 | Commercial Electrical | REQUIRES RESUBMIT | 1.The previous project review comments are not addressed; Please address the electrical plan review comments and provide a written response. Provide detailed information concerning the proposed scope of work. A registrant may be required depending on the scope of work. An aerial photograph of the property and “Remove and replace 400A disconnect switch” is not sufficient information. Is this a service disconnect? What is the voltage, phase and amp ratings? Is this a ‘Like for Like’ replacement? Same location as existing? 2. No comment response letter or explanation submitted. 3. Reconditioned electrical equipment shall comply with NEC 110.21(2). Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC |
||
08/22/2023 | PDSD Application Completeness | REVIEW COMPLETED |