Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0723-01793
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2023 | Commercial Mechanical | NOT REQUIRED | |||
| 08/29/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The Panel schedule for panel ‘A’ and fault current calculations were not found as indicated by the note in the Electrical Riser Diagram. 2 Provide an additional supplemental ground rod if not utilizing a ‘Concrete Encased Grounding Electrode’ per nec art 250.53. 3 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code (OLC) for exterior lighting Lumen and Lamp color Temperature restrictions for the parcel. See Chapter 104 for Permit/Plan Submittal Requirements. Be advised that Luminaires equipped with Full Cut-off shielding as defined per OLC section 202 (Definitions) that are mounted under canopies or roof overhangs are exempt from the lumen calculations per section 401.2.1(3). However, the light source color temperature output cannot exceed 3500K, per section 402.1. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 08/28/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Revise the site plan to show the location of the water meter and the route of the water service to the new kiosk. Reference: Section 107.2.1, IBC 2018. 2. Revise the site plan to show the route and location of the termination of the pumped waste line. Provide a detail of the termination. Reference: Section 107.2.1, IBC 2018 |
||
| 08/29/2023 | Commercial Structural | REQUIRES RESUBMIT | Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Setback requirement is not met against 24th street, please correct this. 2. Parking Stalls are taken out of commission. Please provide the parking calculation, making sure that it still complies to the required parking count. 3. Door Landing width matching door width and 44 inches length. Reflect this on your drawings. 4. Submit your Outdoor Lighting Code analysis and calculation as well as catalog cuts of lioght fixtures being proposed, their specification such as their lumens, color temp, full cutoff or unshielded. 5. Please specify on your roof section drawing as to the material being proposed to provide waterproofing of the concrete slab roof deck, if none...indicate it on the drawing. 6. Please resubmit. |
||
| 07/28/2023 | Site Engineering | REQUIRES RESUBMIT | See zoning comment | ||
| 07/25/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: TC-COM-0723-01793 1300 S 6TH AV Zoning C-3 TRANSMITTAL DATE:July 25, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: er UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://tdc-online.tucsonaz.gov/#/. The DP will need to be approved prior to approval of this building permit. . If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
| 08/28/2023 | Water - PDSD | REQUIRES RESUBMIT | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf | ||
| 07/30/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 07/25/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |