Permit Number: TC-COM-0723-01792
Parcel: 121123540

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01792
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Site Zoning APPROVED
08/29/2023 Commercial Electrical NOT REQUIRED Permit Withdrawn by owner.
09/05/2023 Commercial Mechanical NOT REQUIRED
09/01/2023 Commercial Structural NOT REQUIRED This permit has been withdrawn.
08/03/2023 Site Engineering NOT REQUIRED
09/05/2023 Water - PDSD NOT REQUIRED
09/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/05/2023 Commercial Plumbing REQUIRES RESUBMIT A second natural gas meter is being added to allow separate gas service to the two residence units. Show how the natural gas piping within the building will be split into two systems. Include the gas loads and developed lengths from each meter to all of the gas-fired appliances served by each gas meter. Reference: Section R106.1.1, IRC 2018.
08/04/2023 Fire New Construction REVIEW COMPLETED
08/01/2023 PDSD Application Completeness Express REVIEW COMPLETED