Permit Number: TC-COM-0723-01789
Parcel: 123021860

Address:
2542 E SENECA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01789
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2023 Site Engineering NOT REQUIRED
08/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/28/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/26/2023 1:35:14 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/26/2023 1:33:47 PM
1) Show details for dwelling unit fire-rated separation walls per 2018 IBC Section 420.2.
2) Provide a window schedule detailing if windows are tempered per 2018 IBC Section 2406.4.5.
3) Detail the means of protecting the exterior water piping from freezing per 2018 IPC Section 305.4.
4) Page A-3 is missing exterior receptacles required by 2017 NEC section 210.52(E)(2) and (3). Missing a receptacle on the bedroom/closet wall in Unit B Per 2017 NEC Section 210.52.
5) Include the locations, diagrams, and details for the electrical service main disconnects, feeders, raceways, subpanels, subpanel main disconnects, and grounding.
6) Show the locations of the air conditioners and clarify the locations of the disconnects shown on the electrical floor plans (page A-3).



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/26/2023 1:34:40 PM
See the building review comments.




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/26/2023 1:34:24 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/26/2023 1:34:57 PM
See the building review comments.
07/26/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0723-01789
2542 E SENECA ST Zoning R-1

TRANSMITTAL DATE:‎July 26, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Provide an address for each unit, provide permit documentation for each unit,


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
08/28/2023 Water - PDSD REQUIRES RESUBMIT 1. Provide the size and serial number of the existing water meter. The water calculations indicate that the tri-plex will have a water demand of approximately 21 GPM. Tucson Water requires a ¾” water meter for demands greater than 20 GPM. Reference: Tucson Water Meter Sizing Guidelines, effective 3/2/2020.
2. The water service pipe will need to be increased to maintain a water velocity that is less than 8 feet per second (e.g. 1” Schedule 40 PVC or 1-1/4” PEX). Reference: Section 303.2, IPC 2018.
3. Show the location of the water meter and the water service pipe on the site plan. Reference: Section 107.2.6, IBC.
07/30/2023 Fire New Construction REVIEW COMPLETED
07/25/2023 PDSD Application Completeness Express REVIEW COMPLETED