Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2023 Site Zoning APPROVED
10/16/2023 Water - PDSD NOT REQUIRED
10/16/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 6:36:28 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 6:34:12 PM
1) Sheet A-1 (Proposed Floor Plans): Show details for dwelling unit fire-rated separation walls per 2018 IBC Section 420.2.
Note #3 states that the unit demising wall (between units A and C) is being insulated which would require the removal of the drywall. If the wall surface is being removed, the required fire-rated separation assembly will need to be installed when
replacing the drywall.

2) Sheet A-3 (Electrical Drawings): The panel schedule for subpanel A does not show a minimum of two kitchen counter small appliance circuits. (2017 NEC sections 210.11(C)(1) and 210.52(B)(1))

3) Sheet A-3 (Electrical Drawings - Riser Diagram): Show the equipment grounds are being ran with the feeders from the main disconnects to the subpanels. All service grounding and bonding are to be done only at the main service equipment and the neutrals and grounds are to be separated at the subpanels. (2017 NEC section 250.24(A) and (B))

4) Sheet A-3 (Electrical Drawings - Riser Diagram): Service riser conductors shown as 4/0 aluminum are too small for 300 amps. (2017 NEC Table 310.15(B)(16))

5) Sheet A-3 (Electrical Drawings): Missing a receptacle on the closet wall space between the closet door and the bedroom entrance door in Unit C. (2017 NEC section 210.52)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 6:35:53 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 6:35:01 PM
See the building review comments



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 6:36:12 PM
See the building review comments.