Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0723-01788
Parcel: 10410230D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-0723-01788
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/29/2023 Commercial Mechanical REQUIRES RESUBMIT 1. The current submittal does not have a complete drawing set. The only drawing shown is M2.1; a complete drawing set is required. The ventilation calculations need to be done using the requirements of Section 403.3.1.1, IMC 2018. [Second comment: The City of Tucson has not adopted ASHRAE Standard 62-1 as an approved method for calculating ventilation requirements, the 2018 IMC is the approved method for calculating ventilation requirements. A repair garage has different ventilation requirements compared to an enclosed parking garage and is allowed to reduce the exhaust air flow rate based on the carbon monoxide concentration. Using the AC in a repair garage, will require a plan that considers the air quality (e.g. CO and NOx concentration) in the space.] [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]
2. The existing exhaust system needs to be described to state that the facility can comply with the exhaust requirements whenever the CO/NOx sensors indicate an air quality condition (i.e. 0.75 CFM/square foot). [Second comment: A repair garage requires 0.75 CFM of exhaust per square foot plus source-capture exhaust for running cars (7,500 CFM). 1,000 CFM of make-up air would be inadequate. [Initial comment: Verify that adequate make up air will be provided to offset any required exhaust quantities. Reference: Table 403.3.1.1, IMC 2018.]
08/28/2023 PDSD Application Completeness Express REVIEW COMPLETED