Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4
Permit Number - TC-COM-0723-01787
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/29/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The current submittal has an old copy of drawing M4.1, with no COMcheck, load calculation, or ventilation calculations. Submit a complete, current drawing set. 2. The existing exhaust system needs to be described to state that the facility can comply with the exhaust requirements whenever the CO/NOx sensors indicate an air quality condition (i.e. 0.75 CFM/square foot). The ventilation calculations need to be done using the requirements of Section 403.3.1.1, IMC 2018. [Second comment: The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2018 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.] |
||
08/28/2023 | PDSD Application Completeness | REVIEW COMPLETED |