Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0723-01787
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/03/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/03/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. Reference: Section C503.4, IECC 2018. 2. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 3. Verify that adequate make up air will be provided to offset any required exhaust quantities. Reference: Table 403.3.1.1, IMC 2018. |
||
08/01/2023 | PDSD Application Completeness | REVIEW COMPLETED |