Permit Number: TC-COM-0723-01787
Parcel: 13014023A

Address:
4220 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0723-01787
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2023 PDSD Application Completeness REQUIRES RESUBMIT Please resubmit a site plan showing the location of the replacement and a heating/cooling load calculation. Evaporative coolers with AC units requires submittal of a heating/cooling load calculation to justify the capacities of the units being installed. In addition, structural calculations may be required if the units are located on a roof. Ventilation calculations will be required, and an air balance report is required to verify that the total supply airflow and the outside airflow actually provide the ventilation determined by the calculations.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf