Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0723-01787
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/20/2023 | PDSD Application Completeness | REQUIRES RESUBMIT | Please resubmit a site plan showing the location of the replacement and a heating/cooling load calculation. Evaporative coolers with AC units requires submittal of a heating/cooling load calculation to justify the capacities of the units being installed. In addition, structural calculations may be required if the units are located on a roof. Ventilation calculations will be required, and an air balance report is required to verify that the total supply airflow and the outside airflow actually provide the ventilation determined by the calculations. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |