Permit Number: TC-COM-0723-01771
Parcel: 134100310

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01771
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2023 Site Zoning APPROVED
07/25/2023 Site Engineering NOT REQUIRED
08/14/2023 Water - PDSD NOT REQUIRED
08/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/22/2023 9:21:58 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 3, 4, 5, 8, 9, 10, and 11. Richard P. Canney stamp
expired “6/30/23” on 12 through 17.
2. Special specifications stamped by P.E. Carrie C. Cote expired “3/31/2022.” Provide current stamp/seal/date.
3. Special inspection certificate stamped by P.E. Jennifer M. Patronski expired “7/7/23.” Provide current stamp/seal/date.


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/22/2023 9:22:51 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 3, 4, 5, 8, 9, 10, and 11. Richard P. Canney stamp expired “6/30/23” on 12 through 17.
2. Special specifications stamped by P.E. Carrie C. Cote expired “3/31/2022.” Provide current stamp/seal/date.
3. Special inspection certificate stamped by P.E. Jennifer M. Patronski expired “7/7/23.” Provide current
stamp/seal/date.
4. Sheet 1 of 17 – Provide the list of applicable building codes with City of Tucson amendments.
5. Sheet 1 of 17 – Provide the description of scope under this permit per 2018 International Building Code section 107.


Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/22/2023 9:22:25 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 3, 4, 5, 8, 9, 10, and 11. Richard P. Canney stamp expired “6/30/23” on 12 through 17.



Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/22/2023 9:22:36 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 3, 4, 5, 8, 9, 10, and 11. Richard P. Canney stamp expired “6/30/23” on 12 through 17.


Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/22/2023 9:22:12 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 3, 4, 5, 8, 9, 10, and 11. Richard P. Canney stamp
expired “6/30/23” on 12 through 17.
07/20/2023 Fire New Construction REVIEW COMPLETED
07/19/2023 PDSD Application Completeness Express REVIEW COMPLETED