Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0723-01763
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/30/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | A test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. The balancing shall be performed by a qualified balancing contractor holding certification from the National Environmental Balancing Bureau (NEBB), the Associated Air Balance Council (AABC), or other approved agencies. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson. | ||
| 12/23/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |