Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0723-01763
Parcel: 12215250A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0723-01763
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/30/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT A test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. The balancing shall be performed by a qualified balancing contractor holding certification from the National Environmental Balancing Bureau (NEBB), the Associated Air Balance Council (AABC), or other approved agencies. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson.
12/23/2024 PDSD Application Completeness Express REVIEW COMPLETED