Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/25/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/25/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Provide a detailed description of the proposed scope of work. Provide a site plan showing the location of the electrical equipment on the premises. The feeder for System Pump #1 (Cold Side) is undersized for the 125A OCPD. See NEC Ampacities Table 310.15(B)(16). Should be #1awg Cu. NEC240.4. The feeders feeding Panel ‘HP1’ are also undersized for the 600A OCPD. NEC 240.4, Table 310.15(B)(16). . This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
||
07/19/2023 | PDSD Application Completeness | REVIEW COMPLETED |