Permit Number: TC-COM-0723-01737
Parcel: 14043015B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0723-01737
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/25/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Provide a detailed description of the proposed scope of work.

Provide a site plan showing the location of the electrical equipment on the premises.

The feeder for System Pump #1 (Cold Side) is undersized for the 125A OCPD. See NEC Ampacities Table 310.15(B)(16). Should be #1awg Cu. NEC240.4.

The feeders feeding Panel ‘HP1’ are also undersized for the 600A OCPD. NEC 240.4, Table 310.15(B)(16).

. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
07/19/2023 PDSD Application Completeness REVIEW COMPLETED