Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0723-01714
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2023 | Site Zoning | APPROVED | |||
| 10/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/17/2023 | Water - PDSD | REQUIRES RESUBMIT | 1. Provide verification from Tucson Water that a reduced pressure zone backflow assembly will not be required for this building. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf 2. Show the location and size of the water meter serving this building. Reference: Section 107.2.1 and 107.2.6, IBC 2018 |
||
| 10/04/2023 | External Reviewers - Stantec | REVIEW COMPLETED | |||
| 07/27/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 07/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |