Permit Number: TC-COM-0723-01702
Parcel: 12801005H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01702
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2023 Commercial Electrical APPROVED
08/16/2023 Commercial Structural APPROVED
08/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/10/2023 Commercial Plumbing REQUIRES RESUBMIT Revise the vent for the grease interceptor so it rises vertically to at least 6” above the flood rim of the grease interceptor prior to running horizontally. Reference: Section 905.4, IPC 2018.
07/16/2023 Fire New Construction REVIEW COMPLETED
07/13/2023 PDSD Application Completeness REVIEW COMPLETED