Permit Number: TC-COM-0723-01700
Parcel: 127041480

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01700
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2023 Site Engineering APPROVED
07/19/2023 Site Zoning APPROVED
08/10/2023 Water - PDSD NOT REQUIRED
08/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0723-01700

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/16/2023 4:59:11 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 9, 10, 11, 12, 12A, 12B. Richard P. Canney stamp expired “6/30/23” on 13 through 21.
2. Structural calculation/Electrical equipment rack with optional sunscreens stamped by P.E. Anthony M. Gravagne expired “3/31/2021.”
3. Special specifications stamped by P.E. Carrie C. Cote expired “3/31/2022.”


Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/16/2023 4:58:45 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 9, 10, 11, 12, 12A, 12B. Richard P. Canney stamp expired “6/30/23” on 13 through 21.
2. Structural calculation/Electrical equipment rack with optional sunscreens stamped by P.E. Anthony M. Gravagne expired “3/31/2021”.



Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/16/2023 4:58:26 AM
1. Provide each drawing sheet with currently licensed and unexpired stamp/seal/date from registered design professionals: Carrie C Cote expired “3/31/22” on sheets 2, 9, 10, 11, 12, 12A, 12B. Richard P. Canney stamp expired “6/30/23” on 13 through 21.
07/16/2023 Fire New Construction REVIEW COMPLETED
07/14/2023 PDSD Application Completeness Express REVIEW COMPLETED