Permit Number: TC-COM-0723-01668
Parcel: 112064460

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0723-01668
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/24/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The scope of work per the application is stated as, “Electric meter melted in a fire. No other damage to the unit. Need electric clearance for reconnect”.

And the letter submitted from ‘Tucson Plumbing Solutions’ states that the gas water heaters for units 2451,2455,2457,2459 are going to be replaced with electric water heaters. This being the case. Please apply for permits and submit sealed and complete electrical plans for each address. Calculations and Design are to be performed by a Qualified Registrant registered in the State of Arizona.

Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2018 IBC section 107.1, 107.2.1. 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
07/25/2023 Commercial Plumbing REQUIRES RESUBMIT Provide sealed drawings that clearly show the complete scope of work to be done. Reference: Section 107.2.1, IBC 2018.
07/20/2023 PDSD Application Completeness REVIEW COMPLETED Shared permit documents for permit numbers TC-COM-0723-01666 through TC-COM-0723-01668 under permit number TC-COM-0723-01665 (MAIN).