Permit Number: TC-COM-0723-01667
Parcel: 112064460

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0723-01667
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2023 Commercial Electrical APPROVED
10/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/18/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2, R403.7, and R503.1.2, IECC 2018 as amended by the City of Tucson.
2. Mechanical ventilation is mandatory in dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018.
10/18/2023 Commercial Plumbing REQUIRES RESUBMIT Coordinate the “outlet marks” on the “Mechanical Plan” with the tabular data on sheet P-1 (e.g. the plan shows an outlet 6 but no outlet 3).
10/12/2023 PDSD Application Completeness REVIEW COMPLETED Shared Studio Session 586-515-947 Master Permit TC-COM-0723-01665, TC-COM-0723-01666, TC-COM-0723-01667, TC-COM-0723-01668