Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/12/2023 | Commercial Electrical | APPROVED | |||
10/18/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/18/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2, R403.7, and R503.1.2, IECC 2018 as amended by the City of Tucson. 2. Mechanical ventilation is mandatory in dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018. |
||
10/18/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Coordinate the “outlet marks” on the “Mechanical Plan” with the tabular data on sheet P-1 (e.g. the plan shows an outlet 6 but no outlet 3). | ||
10/12/2023 | PDSD Application Completeness | REVIEW COMPLETED | Shared Studio Session 586-515-947 Master Permit TC-COM-0723-01665, TC-COM-0723-01666, TC-COM-0723-01667, TC-COM-0723-01668 |