Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0723-01660
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The site plan indicates 6 meters and 6 disconnects. This does not correlate with the scope of work details that states replace 100 amp service disconnect. Provide a detailed description of the scope of propose electrical work. If this is not a Like for Like replacement, provide complete electrical plans. Calculations, design are to be performed by a registrant registered in the state of Arizona. Ref 2018 IBC section 107.1, 107.2.1, 2017 NEC |
||
| 07/12/2023 | PDSD Application Completeness Express | REVIEW COMPLETED | Each individual unit requires its own permit. This permit is for (301 W HELEN ST UNIT 4) only, please start new permits for all other units. |