Permit Number: TC-COM-0723-01660
Parcel: 115081990

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0723-01660
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
The site plan indicates 6 meters and 6 disconnects. This does not correlate with the scope of work details that states replace 100 amp service disconnect. Provide a detailed description of the scope of propose electrical work. If this is not a Like for Like replacement, provide complete electrical plans. Calculations, design are to be performed by a registrant registered in the state of Arizona.
Ref 2018 IBC section 107.1, 107.2.1, 2017 NEC
07/12/2023 PDSD Application Completeness Express REVIEW COMPLETED Each individual unit requires its own permit. This permit is for (301 W HELEN ST UNIT 4) only, please start new permits for all other units.