Permit Number: TC-COM-0723-01657
Parcel: 12410004H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0723-01657
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/08/2023 Commercial Structural REQUIRES RESUBMIT Aloha Vince,
It looks like my comments got missed. Allow me to paste them below. (NOTE: Please inform me when you have submitted, allowing me to bring your permit up closer to the top.)
1.) Please coordinate and submit fire sprinkler info to Tucson Fire Department for their review and approval.
2.) Fire alarm per [IBC 907], If they exist...indicate them on your drawing. If
not...please coordinate with Tucson Fire Department.
3.) Illumination with emergency backup power is required in all components of the
means of egress system [IBC 1008]. Please locate those equipments on your plan
(to be inspected by Tucson Fire Department). Electrical work
(conductors/wiring/breaker ONLY) related to the installation of Emergency Lights,
Lighted Signs, Fire/Audible/Smoke Alarms will be inspected by City of Tucson
inspectors, show on your plans so that our inspectors will know what wiring/breaker
to inspect and shall also be reviewed as part of this permit.
4.) Please provide information as to what is being Manufactured by this entity.
5.) Correct your code analysis to include the calculation for the Factory areas
Occupant Load separated from the Business Occupancy. (NOTE: If it is an F or an H or an S...please indicate it within your code analysis.)
08/17/2023 Fire New Construction REVIEW COMPLETED
08/16/2023 PDSD Application Completeness REVIEW COMPLETED