Permit Number: TC-COM-0723-01638
Parcel: 14048003A

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-0723-01638
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2023 Bldg Permits - Post Review REVIEW COMPLETED
11/20/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/6/2023 2:37:17 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/6/2023 10:00:37 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/31/2023 10:14:00 PM
1. The process of “doping,” involving use of a volatile flammable solvent, or of painting, shall be carried on in a separate detached building equipped with automatic fire-extinguishing equipment in accordance with Section 903. (IBC2018,412.4.5) sheet m200 Complied

2. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm for on sheet M200 (IMC2018,606.2.1) Complied

Approved/subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/6/2023 10:27:54 AM
Electrical Review of SkyWest
By: Ron Ross PE
E2.05 POWER PLAN – AREA B: Could not locate Keynote 11.

E2.09 HVAC POWER PLAN - AREA B: Missing Keynotes 5.

E2.15 SPECIAL SYSTEMS PLAN - AREA D: Missing Keynote 7.

E3.00 ONE LINE DIAGRAM & DETAILS: Generator might be undersized for load. Should confirm and upsize if required



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 11/20/2023 8:19:44 AM
Plans are approved. Subject to the field inspector's approval.
11/17/2023 PDSD Application Completeness REVIEW COMPLETED