Permit Number: TC-COM-0723-01638
Parcel: 14048003A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0723-01638
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2025 Commercial Plumbing APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2025 8:20:35 PM
09/29/2025 Site Engineering APPROVED
09/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2025 Commercial Mechanical REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/29/2025 5:11:31 PM
1. (UNRESOLVED) - General - Provide Revision Narrative Letter. The document submitted does not confirm the revision
to the location/Plan Sheet on documents provided. On document, please follow Resubmittal Directions.
i. Provide Narrative Response letter. This response narrative must clearly address how each issue was corrected
or resolved and indicate where the information may be found within the construction documents. The response
narrative must be typewritten, on a letterhead noting the project name, with the Permit Application Number.
Failure to provide this response narrative may result in review delays or rejection of the resubmittal.
▪ Example:
▪ 1. Sheet M-002 - Removed AC-4A from Roof Top Unit Schedule. Added EF-7, EF-23, EF-24 to Exhaust
Fan Schedule. Added Notes 8 & 9 under "Specific Remarks" in the Exhaust Fan Schedule. Removed
Louver SL-6 in the Louver Schedule
▪ 2. Sheet M-003 - Removed AC-4B and AC-7A from Ductless Split System Schedule. Added Return Grill
I in the Air Device Schedule.
09/24/2025 PDSD Application Completeness Express REVIEW COMPLETED