Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0723-01633
Parcel: 12419029C

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0723-01633
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2024 Water Sterilization Report (Deferred Submittal) Express APPROVED
09/23/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The submitted document is not an air balance report, it is a copy of drawing M1which includes the sequence of operation of a CO2 alarm system. Submit an air balance report to verify that the ventilation system is complete and operating as designed. Reference: Section 403.3.1.5, IMC 2018.
09/20/2024 PDSD Application Completeness Express REVIEW COMPLETED